Teléfonos:
(722) 2 80 35 71

   
 
Samwha : Protección : EOCR
   
   
 

 

 

  MCU&ASIC Based Compact Design
  Multiple Protection Functions
  Wide Voltage Adjustment Range
  Digital Volt Meter and Digital Setting
  Trip Cause Display & Easy Troubleshooting
  Manual/Electrical/Automatic Reset
  Adjustable Reset Timer
  Ambient Insensitive
  Panel Mounting type
   
 
Protective Item

Trip Time

Over-voltage

0.5~10 sec

Under-voltage
0.5~10 sec
Phase Loss
2 sec
Phase Reversal
0.1 sec
Phase Unbalance
3sec(If over 5%)
 

Voltage Setting
Range

Type

Over-voltage(O-VOLT)

Under-voltage(U-VOLT)

110

110-150V

80-120V

220

220-300V

160-240V

440

380-500V

300-440V

Trip Time Setting

O-TIME

0.5 ~ 10 sec

U-TIME
0.5 ~ 10 sec

Control Voltage

220

85~250VAC/DC

Others
24,48VAC/DC(Optional Order)

Output Relay

Mode

1-SPDT(1C)

Rating
3A/250VAC Resistive

Status

Normally Energized
Reset
SW3=AUTO
Reset Time:1 or 5sec(DIP-SW4)
SW3=MAN
RESET Button

Mounting

PD

35mm DIN-Rail / Panel

 
   
 
 

:: EOCR de México :: Toluca Estado de México
TEL 2 80 35 71 :: Correo electrónico: direccion@eocr.com.mx ; ventas@eocr.com.mx
Sitio desarrollado por www.mitoluca.com.mx