Teléfonos:
(722) 2 80 35 71

   
 
Samwha : Protección : EOCR
   
   
 

 

 

  MCU( Microprocessor Control Unit ) Based
  DC Motor/DC Device Protection
  Separate Setting for Over-voltage and Undervoltage
  Line Voltage Indicative Function(FND)
  Digital Setting/Trip Cause Indication & troubleshooting
  Auto Reset/Reset Time Setting
  Confirm Setting Value/TEST Function
  No Volt Release Function( Fail-safe Operation)Selectable
 
Protective Item

Trip Time

Over-voltage

0.5~25 sec

Under-voltage
0.5~25 sec
 
Model
DVR
Setting Range
110VDC
220VDC

Over-voltage

OVR

110 - 160V

220 - 320V
Under-voltage
UVR

60 - 110V

160 - 240V
Trip Time

O-TIME

0.5 - 25 sec

Reset Time
R-TIME
0.5 - 25 sec
Power Supply
Voltage
24
24VAC/DC
220
85V - 250VAC/DC
Frequency
50/60Hz
Reset
Manual/Electrical/Auto
Mounting
35mm DIN-Rail/Panel
 
   
 
 

:: EOCR de México :: Toluca Estado de México
TEL 2 80 35 71 :: Correo electrónico: direccion@eocr.com.mx ; ventas@eocr.com.mx
Sitio desarrollado por www.mitoluca.com.mx