Samwha : Protección : EOCR
|
|
|
|
|
|
|
|
 |
|
|
MCU(
Microprocessor Control Unit ) Based Compact Design |
|
Ground (Earth)Fault Protection for
Motor and Power Distribution Systems |
|
Zero Phase Current Detection Method |
|
Test Button Provides a Manual Self-testing Funtion |
|
Independently Adjustable Ground (Earth) Current and
Trip (Operating) Delay Time |
|
Built-in
Power Indication LED and Trip Indication LED |
|
|
|
|
|
|
 |
 |
|
|
Current
Setting
|
0.03~3A(0.03,
0.07, 0.1, 0.3, 0.5, 1, 1.5, 2, 2.5 and 3A Tap)
|
Time
Setting
|
0.2~2.0sec(0.2,
0.4, 0.6, 0.8, 1.0, 1.2, 1.4, 1.6, 1.8 and 2.0sec
Tap)
|
Operating
Characteristic
|
Definite
Time
|
Current
Sensing
|
ZCT(Zero
Phase Current Detection)
|
Control
Voltage
|
240VAC
±10%
|
Frequncy
|
50/60Hz
|
Current
Tolerance
|
±5%
|
Time
Tolerance
|
±5%
|
Output
Contact
|
5A/250VAC
Resistive
|
1-SPDT/Normally
De-energized
|
Rated
Insulation Voltage
|
600VAC,
50/60Hz
|
Expected
Mechanical Life
|
10,000,000
Operation
|
Expected
Electrical Life
|
100,000
Operation
|
Ambient
Temperature
|
-20
~ 60 ¡É
|
Ambient
Humidity
|
10~85%
without Condensation
|
Dielectric
Strength
|
Casing-Circuit
|
2kV,
50/60Hz, 1min
|
Contact-Contact
|
1kV,
50/60Hz, 1min
|
Circuit-Circuit
|
2kV,
50/60Hz, 1min
|
Electrostatic
Discharge
|
IEC61000-4-2
Level-3
|
EFT/Burst
|
IEC61000-4-4
Level-3
|
Surge
|
IEC61000-4-5
Level-3
|
Voltage
Dip & Interruption
|
IEC61000-4-11
|
Mounting
|
Flush
Mount(Panel Door Mount)
|
|
|
|
|
|
|
|
|
|
|
|
|
|