Teléfonos:
(722) 2 80 35 71

   
 
Samwha : Protección : EOCR
   
   
 

 

 

  MCU( Microprocessor Control Unit ) Based Compact Design
  Ground (Earth)Fault Protection for
Motor and Power Distribution Systems
  Residual Current Detection Method
  Test Button Provides a Manual Self-testing Funtion
  Independently Adjustable Ground (Earth) Current and
Trip (Operating) Delay Time
  Built-in Power Indication LED and Trip Indication LED
   
 
Current Setting
0.1~2.5A(0.1, 0.3, 0.5, 0.7, 1.0, 1.3, 1.5, 1.7, 2.0 and 2.5A Tap)
Time Setting
0.2~2.0sec(0.2, 0.4, 0.6, 0.8, 1.0, 1.2, 1.4, 1.6, 1.8 and 2.0sec Tap)

Operating Characteristic

Definite Time

Current Sensing

Residual Current Detection

Control Voltage

240VAC ±10%

Frequncy
50/60Hz
Current Tolerance
±5%
Time Tolerance
±5%
Output Contact
5A/250VAC Resistive
1-SPDT/Normally De-energized
Rated Insulation Voltage
600VAC, 50/60Hz
Expected Mechanical Life
10,000,000 Operation
Expected Electrical Life
100,000 Operation
Ambient Temperature
-20~70℃
Ambient Humidity
10~85% without Condensation
Dielectric Strength
Casing-Circuit
2kv, 50/60Hz, 1min
Contact-Contact
1kv, 50/60Hz, 1min
Circuit-Circuit
2kv, 50/60Hz, 1min
Electrostatic Discharge
IEC61000-4-2 Level-3
EFT/Burst
IEC61000-4-4 Level-3
Surge
IEC61000-4-5 Level-3
Voltage Dip & Interruption
IEC61000-4-11
Mounting
Flush Mount(Panel Door Mount)
 
   
 
 

:: EOCR de México :: Toluca Estado de México
TEL 2 80 35 71 :: Correo electrónico: direccion@eocr.com.mx ; ventas@eocr.com.mx